- A wireless Fluke Connect®-enabled clamp meter designed specifically for the needs of HVAC technicians
- Offers 200 µA DC current measurements to measure flame rod
- Extends resistance range to measure thermistors up to 60kΩ
The post FLUKE 902 FC TRMS HVAC CLAMP METER 600V appeared first on Adex.
]]>3.0 MIN@180 A
> 1.4 MIN@600 A
Add 2% for CF>400 A
Storage: -40 °C to +60 °C (-40 °F to +140 °F)
Storage: 12,000 m (39,370 ft)
IEC 61010-2-032: CAT III 1000 V / CAT IV 600 V
IEC 61010-2-033: CAT III 1000 V / CAT IV 600 V
The post FLUKE 902 FC TRMS HVAC CLAMP METER 600V appeared first on Adex.
]]>- True RMS AC/DC current measurements
- 34mm diameter jaws
- Measures AC current to 600A or 2500A with optional iFlex probes (sold separately)
The post FLUKE 375FC TRUE RMS AC/DC CLAMP METER 600A(1000V) appeared first on Adex.
]]>AC Current via JawRange600.0 AResolution0.1 AAccuracy2% ±5 digits (10 Hz to 100 Hz)2.5% ±5 digits (100-500 Hz)Crest Factor (50 Hz/60 Hz)3 @ 500 A2.5 @ 600 AAdd 2% for C.F. >2AC Current via Flexible Current ProbeRange2500 AResolution0.1 A (≤ 600 A)1 A (≤ 2500 A)Accuracy3% ±5 digits (5 – 500 Hz)Crest Factor (50/60Hz)3.0 at 1100 A2.5 at 1400 A1.42 at 2500 AAdd 2% for C.F. > 2DC CurrentRange600.0 AResolution0.1 AAccuracy2% ±5 digitsAC VoltageRange1000 VResolution0.1 V (≤600.0 V)1 V (≤1000 V)Accuracy1.5% ±5 digits (20 Hz to 500 Hz)DC VoltageRange1000 VResolution0.1 V (≤600.0 V)1 V (≤1000 V)Accuracy1% ±5 digitsmV dcRange500.0 mVResolution0.1 mVAccuracy1% ±5 digitsFrequency via JawRange5.0 Hz to 500.0 HzResolution0.1 HzAccuracy0.5% ±5 digitsTrigger level5 Hz to 10 Hz, ≥10 A10 Hz to 100 Hz, ≥5 A Frequency via Flexible Current ProbeRange5.0 Hz to 500.0 HzResolution0.1 HzAccuracy0.5% ±5 digitsTrigger level5 Hz to 20 Hz, ≥25 A20 Hz to 100 Hz, ≥20 A100 Hz to 500 Hz, ≥25 AResistanceRange60 kΩResolution0.1 Ω (≤600 Ω)1 Ω (≤6000 Ω)10 Ω (≤60 kΩ)Accuracy1% ±5 digitsCapacitanceRange1000 μFResolution0.1 μF (≤ 100 μF)1 μ F (≤ 1000 μF)Accuracy1% ±4 digits
Mechanical Specifications
Maximum voltage between any terminal and earth ground1000 VBatteries2 AA, NEDA 15A, IEC LR6Operating temperature-10 °C to +50 °CStorage temperature-40 °C to +60 °COperating humidity –≤90% RH (at 10 °C to 30 °C)non-condensing (< 10°C)≤75% RH (at 30 °C to 40 °C) Operating altitude3000 mStorage altitude12,000 mSize (L x W x H)249 x 85 x 45 mmWeight395 gJaw opening34 mmFlexible current probe diameter7.5 mmFlexible current probe cable length1.8 m(head to electronics connector)SafetyIEC 61010-1, Pollution Degree 2IEC 61010-2-032: CAT III 1000 V / CAT IV 600 V IP ratingIEC 60529: IP30, non-operatingRadio Frequency Certification FCC IDT68-FBLE IC:6627A-FBLEElectromagnetic Compatibility (EMC)InternationalIEC 61326-1: Portable, Electromagnetic Environment, IEC 61326-2-2CISPR 11: Group 1, Class AGroup 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself.Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power supply network that supplies buildings used for domestic purpose. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances. Emissions that exceed the levels required by CISPR 11 can occur when the equipment is connected to a test object.Korea (KCC)Class A Equipment (Industrial Broadcasting & Communication Equipment)Class A: Equipment meets requirements for industrial electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and not to be used in homes.USA (FCC)47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103.Temperature coefficientsAdd 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C
The post FLUKE 375FC TRUE RMS AC/DC CLAMP METER 600A(1000V) appeared first on Adex.
]]>- Measure, graph, and record PRTs, thermocouples, and thermistors, supporting a wide range of temperature sensors.
- Accuracy up to ±0.002 °C.
- Quick sample readings in as little as 0.3 seconds.
- 1524 has two channels for simultaneous measurements, doubling productivity.
The post FLUKE 1524 HANDHELD THERMOMETER READOUT appeared first on Adex.
]]>| Specifications | |
| Input channels | 2 |
| Logging | 15,000 time and date stamped; 25 readings with statistics |
| Sample interval (normal) |
1 second |
| Sample interval (fast mode) | 0.3 seconds (see technical manual for details) |
| Sensor types | PRTs, RTDs, thermistors, and thermocouples |
| Thermocouple types | C, E, J, K, L, M, N, T, U, B, R, S |
| Operating temperature | -10°C to 60°C (Best accuracy 13°C to 33°C) |
| Power requirements | 3 AA alkaline batteries |
| Size | 96 x 200 x 47 mm (3.75 x 7.9 x 1.86 in) |
| Weight | 0.65 kg (1.4 lb) |
| Environmental conditions for best accuracy | 13°C to 33°C |
| Millivolt range and accuracy | –10 mV to 75 mV ±(0.005% + 5 μV) |
| Resistance range and accuracy | 0 Ω to 400 Ω ±(0.004% + 0.002 Ω) 200 Ω to 50 kΩ ±(0.01% + 0.5 Ω) 50 kΩ to 500 kΩ ± (0.03%) |
| Temperature coefficient, voltage (–10°C to 13°C, +33°C to 60°C) | ±(0.001%/°C + 1 μV/°C) |
| Temperature coefficient, resistance (–10°C to 13°C, +33°C to 60°C) | 0.0008%/°C + 0.0004 Ω (0 Ω to 400 Ω) 0.002%/°C + 0.1 Ω (0 Ω to 50 kΩ) 0.06%/°C + 0.1 Ω (50 kΩ to 500 kΩ) |
| Excitation current, resistance | 1 mA (0 Ω to 400 Ω) 10 μA (0 Ω to 50 kΩ) 2 µA (50 kΩ to 500 kΩ) |
| Thermocouple Equivalent Temperature Accuracies (Readout Only) | |
| Type B | ±0.85°C from 600°C to 800°C ±0.68°C from 800°C to 1000°C ±0.57°C from 1000°C to 1800°C |
| Type C | ±0.32°C from 100ºC to 550°C ±0.71°C from 550°C to 2300°C |
| Type E | ±0.52°C from -200°C to 0°C ±0.22°C from 0°C to 950°C |
| Type J | ±0.52°C from -200°C to 0°C ±0.23°C from 0°C to 1200°C |
| Type K | ±0.61°C from -200°C to 0°C ±0.24°C from 0°C to 1370°C |
| Type L | ±0.36°C from -200°C to 0°C ±0.23°C from 0°C to 1370°C |
| Type M | ±0.26°C from -20°C to 0°C ±0.25°C from 0°C to 400°C ±0.22°C from 400°C to 1400°C |
| Type N | ±0.72°C from -200°C to 0°C ±0.28°C from 0°C to 1300°C |
| Type R | ±1.09°C from -20°C to 0°C ±0.97°C from 0°C to 500°C ±0.49°C from 500°C to 1750°C |
| Type S | ±1.05°C from -20°C to 0°C ±0.95°C from 0°C to 500°C ±0.56°C from 500°C to 1750°C |
| Type T | ±0.60°C from -200°C to 0°C ±0.25°C from 0°C to 400°C |
| Type U | ±0.54°C from -200°C to 0°C ±0.24°C from 0°C to 400°C |
| Accuracies are based on internal reference junction compensation. Refer to technical manual for equivalent accuracies with an external reference junction. | |
| 1524 Accuracies with Selected Probes (±°C) | |
| -200°C | 5616-12: 0.014 5615-6: 0.025 5627A-12: 0.027 5610-9: n/a |
| 0°C | 5616-12: 0.021 5615-6: 0.021 5627A-12: 0.049 5610-9: 0.009 |
| 100°C | 5616-12: 0.027 5615-6: 0.028 5627A-12: 0.065 5610-9: 0.009 |
| 300°C | 5616-12: 0.040 5615-6: 0.043 5627A-12: 0.103 5610-9: n/a |
| 420°C | 5616-12: 0.050 5615-6: n/a 5627A-12: 0.130 5610-9: n/a |
| Includes readout accuracy, probe calibration, and probe drift | |
| PRT Equivalent Temperature Accuracy (Readout only) | |
| –100°C | ±0.011 |
| 0°C | ±0.015 |
| 100°C | ±0.019 |
| 200°C | ±0.023 |
| 400°C | ±0.031 |
| 600°C | ±0.039 |
| Thermistor Equivalent Temperature Accuracy (Readout Only) | |
| 0°C | ±0.002 |
| 25°C | ±0.003 |
| 50°C | ±0.006 |
| 75°C | ±0.014 |
| 100°C | ±0.030 |
The post FLUKE 1524 HANDHELD THERMOMETER READOUT appeared first on Adex.
]]>- True-rms Electronics Logging Multimeter with TrendCapture quickly documents design performance and graphically displays what happened.
- 50;000 count DMM features a large LCD display; 200 hours of data recording; graphical trend display.
- Dual rated CAT IV 600V; CAT III 1000V
The post FLUKE 287-EUR TRUE RMS ELECTRONICS LOGGING MULTIMETER WITH TRENDCAPTURE appeared first on Adex.
]]>FunctionDC voltsRange / resolution50.000 mV, 500.00 mV, 5.0000 V, 50.000 V, 500.00 V, 1000.0 VBasic accuracy0.025%AC voltsRange / resolution50.000 mV, 500.00 mV, 5.0000 V, 50.000 V, 500.00 V, 1000.0 VBasic accuracy0.4% (True-RMS)DC currentRange / resolution500.00 μA, 5000.0 μA, 50.000 mA, 400.00 mA, 5.0000 A, 10.000 ABasic accuracy0.05%AC currentRange / resolution500.00 μA, 5000.0 μA, 50.000 mA, 400.00 mA, 5.0000 A, 10.000 ABasic accuracy0.6% (True-RMS)Temperature (excluding probe)Range / resolution-200.0°C to 1350.0°C (-328.0°F to 2462.0°F)Basic accuracy1.0%ResistanceRange / resolution500.00 Ω, 5.0000 kΩ, 50.000 kΩ, 500.00 kΩ, 5.0000 MΩ, 50.00 MΩ, 500.0 MΩBasic accuracy0.05%CapacitanceRange / resolution1.000 n, 10.00 nF, 100.0 nF, 1.000 μF, 10.00 μF, 100.0 μF, 1000 μF, 10.00 mF, 100 mFBasic accuracy1.0%FrequencyRange / resolution99.999 Hz, 999.99 Hz, 9.9999 kHz, 99.999 kHz, 999.99 kHzBasic accuracy0.005%ConnectivityOptional infrared connector via Fluke ir3000 FCGeneral SpecificationsMaximum voltage between any terminal and earth ground1000 VBattery type6 AA alkaline batteries, NEDA 15A IECLR6Battery life100 hours minimum, 200 hours in logging modeTemperatureOperating-20°C to 55°CStorage-40°C to 60°CRelative humidity0 to 90% (0 t 37°C), 0 to 65% (37°C to 45°C), 0 to 45% (45°C to 55°C)Electromagnetic compatibilityEMC EN61326–1VibrationRandom vibration per MIL-PRF-28800F Class 2Shock1 meter drop per IEC/EN 61010–1 3rd EditionSize (H x W x L)22.2 x 10.2 x 6 cm (8.75 x 4.03 x 2.38 in)Weight870.9 g (28 oz)Multiple on screen displaysYesTrue-RMS AC bandwidth100 kHzdBV/dBmYesDC mV resolution1 μVMegohm rangeUp to 500 MΩConductance50.00 nSContinuity beeperYesBattery/fuse accessYes/YesElapse time clockYesTime of day clockYesMin-max-avgYesPeak250 μsDuty cycle0.01% to 99.99%Pulse width0.025 ms, 0.25 ms, 2.5 ms, 1250.0 msHoldYesIsolated optical interfaceYesAuto/touch holdYesReading memoryYesLog to PCYesInterval/event loggingYesLogging memoryUp to 10,000 readingsWireless connectivity (optional)Yes
The post FLUKE 287-EUR TRUE RMS ELECTRONICS LOGGING MULTIMETER WITH TRENDCAPTURE appeared first on Adex.
]]>- Measure Volts DC; mA; RTDs; thermocouples; frequency; and ohms.
- Source or simulate Volts DC; mA; RTDs; thermocouples; frequency and ohms.
- Optional pressure modules to source/measure pressure
The post FLUKE 725 MULTIFUNCTION PROCESS CALIBRATOR appeared first on Adex.
]]>The post FLUKE 725 MULTIFUNCTION PROCESS CALIBRATOR appeared first on Adex.
]]>- Overall vibration measurement (10 Hz to 1;000 Hz) for acceleration; velocity and displacement units of measurement for a wide variety of machines
- Memory holds up to 3;500 measurements
- Features Fluke Connect
The post FLUKE 805 FC VIBRATION METER WITH FLUKE CONNECT appeared first on Adex.
]]>Low frequency range (overall measurement)10 Hz to 1,000 HzHigh frequency range (CF+ measurement)4,000 Hz to 20,000 HzSeverity levelsGood, satisfactory, unsatisfactory, unacceptableVibration limit50 g peak (100 g peak-peak)A/D converter16-bitSignal to noise ratio80 dBSampling rateLow frequency: 20,000 Hz
High frequency: 80,000 HzReal time clock backupCoin batterySensorSensitivity100 mV g ± 10%Measurement range0.01 g to 50 gLow frequency range (overall measurement)10 Hz to 1,000 HzHigh frequency range4,000 Hz to 20,000 HzResolution0.01 gAccuracyAt 100 Hz ± 5% of measured valueAmplitude UnitsAccelerationg, m/sec²Velocityin/sec, mm/secDisplacementmils, mmInfrared Thermometer (Temperature Measurement)Range-20 °C to 200 °C (-4 °F to 392 °F)Accuracy±2 °C (4 °F)Focal lengthFixed, at ~3.8 cm (1.5″)External SensorNote: Fluke supports but does not provide external sensorsFrequency range10 Hz to 1,000 HzBias voltage (to supply power)20 V dc to 22 V dcBias current (to supply power)Maximum 5 mAFirmwareExternal interfacesUSB 2.0 (full speed) communicationData capacityDatabase on internal flash memoryUpgradeThrough USBMemoryUp to 3,500 measurementsRadiated EmissionElectrostatic discharge: burstStandard EN 61000-4-2Electromagnetic interferenceStandard EN 61000-4-3REStandard CISPR 11, Class AEnvironmentalOperating temperature-20 °C to 50 °C (-4 °F to 122 °F)Storage temperature-30 °C to 80 °C (-22 °F to 176 °F)Operating humidity10% to 95% RH (non-condensing)Operating/storage altitudeSea level to 3,048 meters (10,000 feet)IP ratingIP54Vibration limit500g peakDrop test1 meterGeneral SpecificationsBattery typeAA (2) Lithium Iron DisulfideBattery life250 measurementsSize (L x W x H)24.1 cm x 7.1 cm x 5.8 cm
(9.5 in x 2.8 in x 2.3 in)Weight0.40 kg (0.89 lb)ConnectorsUSB mini-B 7-pin, external sensor jack (SMB connector)
The post FLUKE 805 FC VIBRATION METER WITH FLUKE CONNECT appeared first on Adex.
]]>- Full-featured loop calibrator and 1000V digital multimeter combined into a single handheld unit.
- 20 mA DC current source / loop calibrator / simulator
- Double-sized; dual display
The post FLUKE 789-E PROCESS METER appeared first on Adex.
]]>75% up to 40°C
45% up to 50°C
35% up to 55°C
IEC 1010-1 CAT IV 600 V
1 meter drop test
The post FLUKE 789-E PROCESS METER appeared first on Adex.
]]>- HART Communications capability. Measure: 300V AC/DC; 110mA DC. Source: 15V DC; 22mA DC.
- Measure volts; mA; RTDs; thermocouples; frequency; and ohms to test sensors; transmitters and other instruments
- Bright white dual display. Read both sourced and measured parameters simultaneously.
The post FLUKE 754 HART DOCUMENTING PROCESS CALIBRATOR appeared first on Adex.
]]>100 to 8000.07°C
0.02% + 0.05°C0.14°C
0.04% + 0.10°C200 Ω Pt (385)-200 to 100
100 to 6300.07°C
0.02% + 0.05°C0.14°C
0.04% + 0.10°C500 Ω Pt (385)-200 to 100
100 to 6300.07°C
0.02% + 0.05°C0.14°C
0.04% + 0.10°C1000 Ω Pt (385)-200 to 100
100 to 6300.07°C
0.02% + 0.05°C0.14°C
0.04% + 0.10°C100 Ω Pt (3916)-200 to 100
100 to 6300.07°C
0.02% + 0.05°C0.14°C
0.04% + 0.10°C100 Ω Pt (3926)-200 to 100
100 to 6300.08°C
0.02% + 0.06°C0.16°C
0.04% + 0.12°C10 Ω Cu (427)-100 to 2600.2°C0.4°C120 Ω Ni (672)-80 to 2600.1°C0.2°CSource currentSource °CAllowable current2 1 year2 year 1 mA0.05°C
0.0125% + 0.04°C0.10°C
0.025% + 0.08°C0.1 mA to 10 mA500 μA0.06°C
0.017% + 0.05°C0.12°C
0.034% + 0.10°C0.1 mA to 1 mA250 μA0.06°C
0.017% + 0.05°C0.12°C
0.034% + 0.10°C0.1 mA to 1 mA150 μA0.06 C
0.017% + 0.05°C0.12 C
0.034% + 0.10°C0.1 mA to 1 mA1 mA0.05°C
0.0125% + 0.04°C0.10°C
0.025% + 0.08°C0.1 mA to 10 mA1 mA0.05°C
0.0125% + 0.04°C0.10°C
0.025% + 0.08°C0.1 mA to 10 mA3 mA0.2°C0.4°C0.1 mA to 10 mA1 mA0.04°C0.08°C0.1 mA to 10 mA1. For two and three-wire RTD measurements, add 0.4°C to the specifications.
2. Supports pulsed transmitters and PLCs with pulse times as short as 1 msTemperature, ThermocouplesTypeSource °CMeasure °CSource °C 1 year2 years1 year2 yearsE-250 to -2001.32.00.60.9-200 to -1000.50.80.30.4-100 to 6000.30.40.30.4600 to 10000.40.60.20.3N-200 to -1001.01.50.60.9-100 to 9000.50.80.50.8900 to 13000.60.90.30.4J-210 to -1000.60.90.30.4-100 to 8000.30.40.20.3800 to 12000.50.80.30.3K-200 to -1000.71.00.40.6-100 to 4000.30.40.30.4400 to 12000.50.80.30.41200 to 13720.71.00.30.4T-250 to -2001.72.50.91.4-200 to 00.60.90.40.60 to 4000.30.40.30.4B600 to 8001.32.01.01.5800 to 10001.01.50.81.21000 to 18200.91.30.81.2R-20 to 02.32.81.21.80 to 1001.52.21.11.7100 to 17671.01.50.91.4S-20 to 02.32.81.21.80 to 2001.52.11.11.7200 to 14000.91.40.91.41400 to 17671.11.71.01.5C0 to 8000.60.90.60.9800 to 12000.81.20.71.01200 to 18001.11.60.91.41800 to 23162.03.01.32.0L-200 to -1000.60.90.30.4-100 to 8000.30.40.20.3800 to 9000.50.80.20.3U-200 to 00.60.90.40.60 to 6000.30.40.30.4BP0 to 10001.01.50.40.61000 to 20001.62.40.60.92000 to 25002.03.00.81.2XK-200 to 3000.20.30.20.5300 to 8000.40.60.30.6
The post FLUKE 754 HART DOCUMENTING PROCESS CALIBRATOR appeared first on Adex.
]]>- Loop calibrator that measures 4 to 20 mA signals without breaking the loop
- Features best in class 0.2% accuracy
- Sources 4 to 20 mA signals for testing control system I/O or I/Ps
The post FLUKE 773 ADVANCED MILLIAMP PROCESS CLAMP-METER appeared first on Adex.
]]>(< 18ºC or > 28ºC)
One year for cable and clamp assembly
(measured by clamp)
The post FLUKE 773 ADVANCED MILLIAMP PROCESS CLAMP-METER appeared first on Adex.
]]>- Earth ground ac leakage current measurement
- Heavy-duty clamp jaw stays in alignment and in calibration even in every day, on-the-job industrial environments.
- Identify ac leakage currents without disconnecting the earth ground stake from the grounding system–ideal for system troubleshooting.
The post FLUKE 1630-2 FC EARTH GROUND CLAMP METER 1000V appeared first on Adex.
]]>| Electrical Specifications | ||
| Maximum voltage to earth ground | 1000 V | |
| Battery type | AA alkaline IEC/EN LR6 (x4) | |
| Battery life | More than 15 hours* | |
| * In Ground Resistance measurement mode, with backlight turned off, and RF mode turned off | ||
| Frequency range | 40 Hz to 1 kHz | |
| Ingress protection | IEC/EN 60529: IP30 with jaw closed | |
| LCD | Digital reading | 9999 counts |
| Refresh rate | 4 per second | |
| Operating temperature | -10 °C to + 50 °C | |
| Storage temperature | -20 °C to + 60 °C | |
| Operating humidity | Non condensing (<10 °C) (< 50 °F) | |
| ≤90% RH (at 10 °C to 30 °C [50 °F to 86 °F]) | ||
| ≤75% RH (at 30 °C to 40 °C [86 °F to 104 °F]) | ||
| ≤45% RH (at 40 °C to 50 °C [104 °F to 122 °F]) | ||
| (Non condensing) | ||
| Operating altitude | 2000 m (6561 feet) | |
| Storage altitude | 12 000 m (39,370 feet) | |
| Reference temperature | 23 °C ±5 °C (73 °F ±9 °F) | |
| Temperature coefficient | 0.15% x (specified accuracy)/ °C (<18 °C or >28 °C [<64.4 °F or >82.4 °F]) | |
| Overload indication | OL | |
| Data logging capacity | Minimum of 32,760 measurements | |
| Data logging interval | 1 second to 59 minutes and 59 seconds | |
| Display reading specification with standard loop resistance | ||
| Input (Ω) | Minimum | Maximum |
| 0.474 | 0.417 | 0.531 |
| 0.5 | 0.443 | 0.558 |
| 10 | 9.55 | 10.45 |
| 100 | 96 | 104 |
| Safety | ||
| General | IEC/EN 61010-1: Pollution Degree 2 IEC/EN 61557-1 | |
| Measurement | IEC/EN 61010-2-032: CAT IV 600 V / CAT III 1000 V | |
| Current clamp for leakage current measurements | IEC/EN 61557-13: Class 2, ≤30 A/m | |
| Resistance to earth | IEC/EN 61557-5 | |
| Effectiveness of thepProtective measures | IEC/EN 61557-16 | |
| Electromagnetic compatibility (EMC) | International | IEC/EN 61326-1: Portable Electromagnetic Environment |
| CISPR 11: Group 1, Class B, IEC/EN 61326-2-2 | ||
| Korea (KCC) | Class A equipment (Industrial Broadcast & Communications Equipment) | |
| USA (FCC) | 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103 | |
| Wireless Radio | ||
| Frequency range | 2412 MHz to 2462 MHz | |
| Output power | <10 mW | |
| Radio frequency certification | FCC ID:T68-FBLE IC:6627A-FBLE | |
| General Specifications | ||
| Conductor size | 40 mm (1.57 in) approximately | |
| Dimensions (L x W x H) | 283 x 105 x 48 mm (11.1 x 4.1 x 1.9 in) | |
| Weight | 880g (31 oz) | |
| Warranty | One year | |
| Earth Ground Loop Resistance | ||
| Range | Accuracy1 ± (% of reading + Ω) | |
| 0.025 Ω to 0.249 Ω | 1.5% + 0.02 Ω | |
| 0.250 Ω to 0.999 Ω | 1.5% + 0.05 Ω | |
| 1.000 Ω to 9.999 Ω | 1.5% + 0.10 Ω | |
| 10.00 Ω to 49.99 Ω | 1.5% + 0.30 Ω | |
| 50.00 Ω to 99.99 Ω | 1.5% + 0.50 Ω | |
| 100.0 Ω to 199.9 Ω | 3.0% + 1.0 Ω | |
| 200.0 Ω to 399.9 Ω | 5.0% + 5.0 Ω | |
| 400 Ω to 599 Ω | 10.0% + 10 Ω | |
| 600 Ω to 1500 Ω | 20.00% | |
| 1 Loop resistance with no inductance, conductor centered and perpendicular to jaw | ||
| Earth ground leakage current mA | ||
| Autorange 50/60 Hz, True rms, crest factor CF ≤3 | ||
| Range | Resolution | Accuracy1 ± (% of reading + mA) |
| 0.200 mA to 3.999 mA | 1 μA | 2.0% + 0.05 mA |
| 4.00 mA to 39.99 mA | 10 μA | 2.0% + 0.03 mA |
| 40.0 mA to 399.9 mA | 100 μA | 2.0% + 0.3 mA |
| 0.400 A to 3.999 A | 1 mA | 2.0% + 3 mA |
| 4.00 A to 39.99 A | 10 mA | 2.0% + 30 mA |