Hioki portable battery testers support the maintenance of UPS and storage batteries critical to the life support of all businesses. The BT3554-50 battery internal resistance tester sets the standard for assessing the deterioration and remaining life of UPS and other lead-acid batteries by giving a complete diagnosis via battery resistance testing. The specially designed L2020 Pin Type Lead further improves testing efficiency with an L-shaped tip that lets you reach deep into the battery racks to completely probe the terminals.
Hioki Battery Tester BT3554-50
Hioki BT3554 Battery tester is an impedance tester, designed for UPS and lead-acid battery diagnostics, accurately measuring the internal impedance of rechargeable batteries including lead-acid, lithium-ion, nickel-cadmium etc.
There are different probe variations coming along with the BT3554 machine namely BT3554-50 , BT3554-51, BT3554-52 , BT3554-91 and BT3554-92 .
Resistance measurement range | 3 mΩ (max. display 3.100 mΩ, resolution 1 μΩ) to 3 Ω (max. display 3.100 Ω, resolution 1 mΩ), 4 ranges |
---|---|
Voltage measurement range | ± 6 V (max. display ±6.000 V, resolution: 1 mV) to ± 60 V (max. display ±60.00 V, resolution: 10 mV), 2 ranges, Accuracy: ±0.08 % rdg ±6 dgt |
Temperature measurement accuracy | Measurement range: -10°C to 60°C (14°F to 140°F), Maximum display: 60.0°C (140.0°F), Resolution 0.1°C (0.1°F), Measurement accuracy*: ±1.0°C (±1.8°F) |
Absolute max. input voltage | 60 V DC max. (No AC input) |
Measurement time | 100 ms |
Response time | Approx. 1.6 sec. |
Comparator | Compares measured values with set threshold values to make judgments and reports them to the user. |
Memory functionality | Operation: Save, load, and delete measurement data, Save and delete profile information, Number of data sets: 6000, Memory architecture: 500 data sets per unit (12 units) 1. Measurement data: Data can be saved, loaded, and deleted by operating the instrument. 2. Profile information: Profile information can be saved, loaded, and deleted using a supported application (GENNECT Cross or GENNECT One). |
Measurement Navigator | Operation: Announces the next battery number to be measured via a screen display and audio guidance. |
Communication interface | USB |
Other functions | Temperature measurement (-10.0 to 60.0 °C), Zero-adjustment, Hold, Auto-hold, Auto-memory, Auto-power-save, Clock |
Power supply | LR6 (size AA) alkaline battery ×8 |
Dimensions and mass | 199 mm (7.83 in)W × 132 mm (5.20 in)H × 60.6 mm (2.39 in)D (with protector), 960 g (33.9 oz) (including batteries and protector) |
Accessories | Carrying Case C1014 ×1, Protector Z5041 ×1, Fuse Set Z5050 ×1, 0 Adj Board ×1, Neck strap ×1, USB cable ×1, Application software CD (GENNECT One) ×1, AA alkaline battery (LR6) ×8, User Manual ×1 |