Adapter for measurement terminal (MODEL 8259)
Adapter to enable use of ather test leads.
Earth resistance measurement |
20Ω | 200Ω | 2000Ω | ||||
---|---|---|---|---|---|---|---|
Measuring range | 0.00 – 2000 Ω | ||||||
Display range | 0.00 – 20.99 Ω | 0.0 – 209.9 Ω | 0 – 2099 Ω | ||||
Accuracy*1 | ±1.5%rdg±0.08 Ω*2 | ±1.5%rdg±4dgt | |||||
Auxiliary earth resistance*3 | <10kΩ | <50kΩ | <100kΩ | ||||
Comparator reference value | 10Ω | 100Ω | 500Ω | ||||
Earth voltage measurement | |||||||
Measuring range | 0 – 300 V AC (45 – 65Hz) | ±0 – ±300 V DC | |||||
Display range | 0.0 – 314.9 V | 0.0 – ±314.9 V | |||||
Accuracy | ±1%rdg±4dgt | ||||||
Applicable Standards | IEC 61010-1 CAT Ⅳ 100V / CAT Ⅲ 150V / CAT Ⅱ 300V Pollution degree 3 IEC 61010-2-030, IEC 61010-031, IEC 61557-1, 5 IEC 60529 (IP67), IEC 61326-1, 2-2 |
||||||
Communication interface | Bluetooth® Ver.5.0 | ||||||
Power source | LR6(AA)(1.5V) × 6 | ||||||
Dimensions | 121(L) × 188(W) × 59(D) mm (including case lid) | ||||||
Weight | Approx. 690g (including batteries and case lid) | ||||||
Included Accessories | 7127B (Simplified measurement probe) 7266 (Earth resistance test leads [red:20m, yellow:10m, green:5m/1set]) 8041 (Auxiliary earth spikes [2 spikes/1set]) 9121 (Shoulder strap) 9197 (Hard case) LR6(AA) × 6, Instruction manual |
||||||
Optional Accessories | 7267 (Cable reel for Earth resistance tester [red:20m]) 7268 (Cable reel for Earth resistance tester [yellow:10m]) 7271 (Earth resistance test lead [green:5m]) 7272 (Precision measurement cord set) 8259 (Adapter for measurement terminal) 9190 (Carrying case) |
*1 For precision measurement, auxiliary earth resistance should be 100 Ω ±5% or less.
*2 At simplified measurement add ±0.10 Ω to the specified accuracy.
*3 Accuracy within the auxiliary earth resistance: ±5% rdg ±10 dgt.